Technical Specifications
- Power Supply:
• Power AC 110/220VAC, 50-60Hz Manual switching
• Power DC 18 to 32 VDC (+/-10%) Typical 24VDC
- Power Consumption Max 105W (including detector and external devices), max 210W with expansion unit
- Available I/O Modules: 4-20mA Input 2 or 3 wire, 2/4/8 channel modules,10/12/16 with expansion unit
- mV Input: Catalytic type flammable gas detectors(Honeywell models). 2/4/8 channel modules, 10/12/16 with expansion unit
- Dual Input: 2 channel mA + 2 channel mV module or 4 channel mA + 4 channel mV module
- Relay Output: 12 or 24 relay outputs, NO/C/NC changeover, 1.7A@30VDC/250VAC,user configurable - energised/de-energised,latching/non latching, time delay
- 4-20mA Output:4 or 8 isolated repeated mA outputs,
0-22mA, 0-100%FSD = 4-20mA
- Common Inputs: Remote reset, remote inhibit
- Common Outputs: Four powered A/V outputs for alarms and fault, three common alarm outputs
- Data logging :Configuration, logged events and data
- Communication :MODBUS TCP, WEB monitoring and
MODBUS RTU
|
General Specifications
- Capacity Up to 8 channels with base unit, up to 16
channels with expansion unit.
- Display: 7’’colour LCD touchscreen. Graphic User Interface
- Audible Alarm = 70dB @ 1m
- Button: Common for reset/mute operation
- Language: English, French, German, Italian, Dutch,
Spanish, Portuguese, Russian, Chinese
- Operating: -10 °C to +55 °C (14 °F to +131 °F) continuous, up to 95% RH
- Approval: Electromagnetic Compatibility and Electrical Safety
• EMC/RFI (EN 50270:2015)
• LVD (EN 61010-1:2010)
• CSA-C22.2 No. 61010-1-04
• UL 61010-1 (3rd Edition) and 508
- Safety Integrity :IEC 61508:2010 Ed.2 SIL2, EN
50271:2010
- Hazardous Location: Class I, Division 2, Group A, B, C and D or non-hazardous only
|