Technical Specifications
- Power Supply: • Power AC 110/220VAC, 50-60Hz Manual switching • Power DC 18 to 32 VDC (+/-10%) Typical 24VDC - Power Consumption Max 105W (including detector and external devices), max 210W with expansion unit - Available I/O Modules: 4-20mA Input 2 or 3 wire, 2/4/8 channel modules,10/12/16 with expansion unit - mV Input: Catalytic type flammable gas detectors(Honeywell models). 2/4/8 channel modules, 10/12/16 with expansion unit - Dual Input: 2 channel mA + 2 channel mV module or 4 channel mA + 4 channel mV module - Relay Output: 12 or 24 relay outputs, NO/C/NC changeover, 1.7A@30VDC/250VAC,user configurable - energised/de-energised,latching/non latching, time delay - 4-20mA Output:4 or 8 isolated repeated mA outputs, 0-22mA, 0-100%FSD = 4-20mA - Common Inputs: Remote reset, remote inhibit - Common Outputs: Four powered A/V outputs for alarms and fault, three common alarm outputs - Data logging :Configuration, logged events and data - Communication :MODBUS TCP, WEB monitoring and MODBUS RTU
|
General Specifications
- Capacity Up to 8 channels with base unit, up to 16 channels with expansion unit. - Display: 7’’colour LCD touchscreen. Graphic User Interface - Audible Alarm = 70dB @ 1m - Button: Common for reset/mute operation - Language: English, French, German, Italian, Dutch, Spanish, Portuguese, Russian, Chinese - Operating: -10 °C to +55 °C (14 °F to +131 °F) continuous, up to 95% RH - Approval: Electromagnetic Compatibility and Electrical Safety • EMC/RFI (EN 50270:2015) • LVD (EN 61010-1:2010) • CSA-C22.2 No. 61010-1-04 • UL 61010-1 (3rd Edition) and 508 - Safety Integrity :IEC 61508:2010 Ed.2 SIL2, EN 50271:2010 - Hazardous Location: Class I, Division 2, Group A, B, C and D or non-hazardous only
|